Fire Rated Partitions for Industrial Buildings
A fire rated partition is not a stronger version of an ordinary wall. It is a tested system, built exactly as tested, that holds back fire for a set time so people can get out and the fire stays where it started.
These jobs usually involve building control, so the price and the programme are set once the fire strategy is clear.
- Rated by
- Tested system, as installed
- Approval
- Usually building control
- Price
- Set on survey
When you need one
- A new compartment wall in a large storage building
- Protected escape routes and corridors
- Plant rooms and stores that hold a higher fire risk
- An office or welfare block built inside a production hall
Not the right choice for: Mesh of any kind, which gives no fire resistance; Any panel without test evidence for the way it will be built.
Why this is building work
Regulation 3 of the Building Regulations 2010 (England and Wales) treats a "material alteration" as building work. That is work which would leave the building failing, or failing more than before, against certain requirements, and those include the fire requirements on means of warning and escape and on internal fire spread through the structure.
A wall that forms part of a fire compartment or protects an escape route touches both. In England the guidance sits in Approved Document B, volume 2, which covers buildings other than dwellings. Wales publishes its own Part B guidance, and Scotland works through building warrants under its own regulations.
You can apply with full plans or, for some work, a building notice. GOV.UK sets out how to apply. On a fire wall, full plans gives you the answer before anything is built.
What a fire resistance rating tells you
A rating says how long a tested specimen kept doing its job in a standard fire test. Under the European classification, BS EN 13501-2, a partition might be shown as E for integrity (keeping flames and hot gas back) and I for insulation (keeping the far side cool enough), followed by minutes, for example EI 60.
The rating belongs to the system as tested: the panel, the frame, the doors, the glazing, the seals and the way it is fixed to the floor and roof. Swap one part, or leave a gap where a pipe passes through, and the evidence no longer covers what you have built.
- Ask for the test or assessment report, not a brochure line.
- Check the doors and glazing are covered by the same evidence.
- Plan penetrations now, with a tested sealing method for each one.
Keep that evidence with your building records. It is the first thing a fire risk assessor or a future buyer will ask for.
Once the wall is up
The Fire Safety Order puts duties on the responsible person for the premises. The fire risk assessment has to be reviewed when there is a significant change (article 9), escape routes must be kept clear, and fire precautions maintained in working order. GOV.UK sums these up in workplace fire safety: your responsibilities.
In practice that means checking the wall stays complete: no new holes cut for cables, fire doors closing properly, and seals in place.
How a fire rated job runs
Fire strategy
Agree what the wall must do and for how long, with your fire engineer or assessor where you have one.
System and approval
A tested system is chosen and plans go to building control.
Install as tested
Panels, doors, glazing and seals fitted to the test evidence, with penetrations sealed.
Sign-off and records
Building control completion, the evidence filed, and the risk assessment reviewed.
Fire rated partition questions
Is mesh partitioning ever fire rated?
No. Open mesh lets fire and smoke through and has no fire resistance.
What does EI 60 mean?
Under BS EN 13501-2, E is integrity and I is insulation. EI 60 means the tested system kept both for 60 minutes in the standard test.
Do I need building regulations approval for a fire rated partition?
Usually, yes. A wall that forms part of the fire separation or an escape route is likely to be a material alteration under regulation 3, so it is building work.
Does a new fire wall mean a new fire risk assessment?
The existing assessment must be reviewed when there is a significant change in the premises (article 9). A new compartment wall usually counts.
How much does a fire rated partition cost?
It depends on the rating, the height, the doors and glazing, and the penetrations. There is no published rate we can stand behind, so it is priced on survey.
Related pages
Rules and guidance we drew on
- The Building Regulations 2010 (England and Wales), regulation 3: meaning of building work (legislation.gov.uk)
- Fire safety: Approved Document B, volume 2 covers buildings other than dwellings (GOV.UK)
- Building regulations guidance Part B, volume 2, Wales (gov.wales)
- How to apply for building regulations approval (GOV.UK)
- Fire Safety Order, article 9: risk assessment (legislation.gov.uk)
- Workplace fire safety: your responsibilities (GOV.UK)
Get prices for a fire rated wall
We look for an installer who fits this kind of system near your site and tell you who they are before any of your details go to them. There is no charge to you.
Thank you. Your enquiry has reached us.
- We look for an installer who fits this kind of system in your part of the country.
- We tell you who they are. Your details only go to them if you say yes.
- They arrange a survey and send a written price. We send no marketing.